Volume Control Dampers

Introduction

Silent Features

ALUGRIDX Opposed Blade / Parallel Blade Volume Control Dampers are designed for air volume flow and pressure control or to isolate sections of ducting in the air-conditioning and ventilation system.

Galvanized sheet steel casing with airfoil blades connected by linkage with manual operation by quadrant.

Constructional Details

Frame: Galvanized sheet steel 1.2 mm thickness

Blades: Aluminum fixed profile airfoil blades 1 mm / 1.2 mm thickness

Bearings: PVC / Nylon bush

Shaft: Galvanized steel

Quadrant: Locking type with position indicator

General: All joints are welded and sealed for air-tight operation and all welded joints are protected by aluminum spray coating

Available Finishes

• Galvanized sheet steel frame

• Epoxy primary coated finish

Available Standard Sizes

L15020030040050060070080090010001200
10020030040050060070080090010001200

Available Standard Types & Models

MODELNOMENCLATUREACCESSORIESS
CDO - SOpposed blade damper with slip on fixing
CDP - SParallel blade damper with slip on fixing
CDO - FOpposed blade damper with flange fixing
CDP - FParallel blade damper with flange fixing
CDO - COpposed blade damper with 'C' cleat fixing
CDP - CParallel blade damper with 'C' cleat fixing

Dimensional Data

Technical Data

Installation Corrrection Factor

Blade angleBCD
6.04.09.0
15°4.32.96.3
30°2.01.72.7
45°1.41.41.8

Example

Given: Type D installation

X = 15°

V = 4 m/sec

Result: Pr. Drop (D) = Pr. Drop (A) x 6.3

= 5 x 6.3

= 31.5 Pa

Circular VCD

Available Standard Sizes

D (mm) LeftD (mm) Right
100315
125350
150400
160450
200500
250600
300

VD-R/G : Circular Volume Control Damper with Grooved Ends

VD-R/S : Circular Volume Control Damper with Straight Ends

ALUGRIDX Models VD-RG and VD-RS are Circular Volume Control Dampers designed to regulate air volume through round ducts.

The casing and the blade are made from galvanized steel sheets.

The adjustable damper blades are mounted on Nylon Bushes with a manually operated quadrant set.

The movement of the blades allows regulation from fully open to almost complete shut off.

Useful Conversion Factors

MultiplyByTo GetMultiplyByTo Get
mm0.0393in.in.25.4mm
mm3.2807ft.ft.0.3048mm
m210.764ft2ft20.0929m2
m335.31ft.3ft.30.0283m3
m3/sec1000--0.001m3/sec
m3/sec2119.5cfmcfm0.00047m3/sec
m3/h0.5886cfmcfm1.6986m3/h
m3/min35.32cfmcfm0.0284m3/min
l/sec2.1195cfmcfm0.4719l/sec
m3/sec264.18gpm (U.S.)gpm (U.S.)0.00378m3/sec
m3/h4.403gpm (U.S.)gpm (U.S.)0.2268m3/h
l/sec15.85gpm (U.S.)gpm (U.S.)0.063l/sec
m/sec196.8fpmfpm0.0051m/sec
m/sec3.28fpsfps0.3048m/sec
Kg2.2046lbslbs0.4536Kg
Kg15456graingrain0.00006Kg
N0.102Kg(kp)Kg(kp)9.8066N
N0.2248lb. flb. f4.4482N
Pa1N/m2N/m21Pa
Pa0.000145psipsi6896Pa
Pa0.000295in. Hg.in. Hg.3386Pa
Pa0.0041in. WGin. WG249Pa
Pa0.00033ft. WGft. WG2989Pa
Pa0.00001barbar10000Pa
Pa0.102mm. WGmm. WG9.8066Pa
Pa0.0001m. WGm. WG980.66Pa
Pa0.00001AtAt98066Pa
Pa0.00001Kg/cm2Kg/cm298066Pa
Kg/cm214.223psipsi0.0703Kg/cm2
Pa0.0075Tr.Tr.133.3Pa
Kcal/hr.3.968BTU/hr.BTU/hr.0.2519Kcal/hr.
Kcal/hr.0.00033Ref.tonRef.ton3022.8Kcal/hr.
W1J/sJ/s1W
W0.861Kcal./hrKcal./hr1.163W
W3.412BTU/hr.BTU/hr.0.2931W
kW0.285Ref.tonRef.ton3.517kW
kW1.36HpmetricHpmetric0.7354kW
kW1.341HP (UK)HP (UK)0.7457kW
cal4.1858JJ0.2389cal
BTU1111JJ0.0009BTU
kWh3.6MJMJ0.2778kWh
kGm9.8087JJ0.102kGm
ft. lb.1.3558JJ0.7376ft. lb.
Kcal/kg4.1868kJ/kgkJ/kg0.2388Kcal/kg
BTU/lb2.326kJ/kgkJ/kg0.4299BTU/lb
lb/lb1kg/kgkg/kg1lb/lb
grain/lb0.143g/kgg/kg6.993grain/lb
m3/kg16.018ft.3/lbft.3/lb0.0624m3/kg
m2degC hr.5ft.2degC hr.ft.2degC hr.0.2m2degC hr.
Kcal-BTUBTU-Kcal

Terminal Units (VAV)

DESCRIPTION

The specialized low-pressure bypass terminal unit has been intricately crafted to provide the capacity for controlling temperatures across multiple zones in air systems with low and medium airflow velocities. It adjusts its functioning in direct response to the cooling demands by modulating the volume of air supplied to the conditioned space. It releases conditioned air into the area precisely during periods of maximum cooling loads, as determined by the thermostat’s settings.

As the need for cooling decreases, the model undergoes modulation to redirect the conditioned air towards the return ceiling plenum or duct. This consistent adjustment ensures a steady air volume throughout the central system while simultaneously allowing for variable air volume delivery to the designated space.

Technical Data

CONSTRUCTION

Consists of an external casing made of 1.0 mm galvanized steel acoustically and thermally insulated with 1” glass fiber material.

SIZEMAX. CFMABCEF
1200250 (10)200 (8)400175 (7)100 (4)
2400300 (12)250 (10)400225 (9)150 (6)
3600350 (14)300 (12)550275 (11)250 (10)
4800400 (16)350 (14)550325 (13)250 (10)
51200450 (18)400 (16)600375 (15)275 (11)
61500500 (20)450 (18)600450 (18)150 (6)
72400600 (24)500 (20)600550 (22)150 (6)
83200800 (32)550 (22)600750 (30)150 (6)